Back to Search

Correct Electrical Deficiencies

VETERANS AFFAIRS, DEPARTMENT OF

Description

<p>SOW&nbsp;<br />
565-22-500 Correct Electrical Deficiencies&nbsp;<br />
Fayetteville VAMC</p>

<p>Intent<br />
The project consists of correcting electrical deficiencies as noted from previous VA facility assessments. Improvements include; New electrical entrance building, medium voltage loop replacement, replace electrical distribution equipment, ground conductor corrections, incidental electrical equipment cleanup throughout the Fayetteville VAMC, and minor HVAC and Plumbing improvements. &nbsp;Period of performance 1,174 calendar days.<br />
Medium Voltage<br />
VA owned medium voltage loop and entrance equipment will be modified or replaced with the following scope:<br />
Replace existing medium voltage entrance equipment with new at campus entrance.&nbsp;<br />
Provide new building:<br />
Slab on grade, brick on CMU wall, Slate roof tile (to match existing facility)<br />
Provide new VA owned medium voltage cables in concrete encased duct bank for medium voltage loop. Approximately 300 .<br />
Demo and remove old VA owned medium voltage entrance metal shack.<br />
Replace medium voltage sectionalized switch.&nbsp;<br />
Provide new metal-clad switchgear with draw-out vacuum circuit breakers.<br />
Replace medium voltage oil filled transformer (1)<br />
Panel Replacement and Branch Circuit Improvements<br />
Correct deficiencies to electrical panels and branch circuit wiring which are not correctly sized, protected, or are at end of useful life, as identified through various inspections over the years. o&nbsp;</p>

<p>All work will be phased. All replacements to existing equipment will require the contractor to filled-out a phasing plan for VA approval. All replacements to existing equipment will require a temporary power solution to minimize electrical outage to existing areas. Such deficiencies include:<br />
Replace-in-same-room building entrance and large distribution equipment:<br />
Normal (service entrance) Switchboards: approx. 2&nbsp;<br />
Generator switchboards: approx. 2&nbsp;<br />
Automatic transfer switch: approx. 7<br />
Replace-in-place distribution panels and panelboards distribution equipment<br />
Distribution Panels: approx. 5<br />
Panelboards: approx. 68<br />
Replace undersized feeders<br />
Redundant Gound<br />
Provide redundant equipment grounding conductor to a portion of the facility.<br />
Approx. 100,000 square feet of existing electrical branch circuit distribution in occupied space.&nbsp;<br />
HVAC And Plumbing<br />
Reroute (vertically &amp; horizontally) Sewer piping and hot water piping to avoid electrical room.<br />
Provide exhaust fan to new Medium Voltage building.&nbsp;<br />
Incidental Electrical Equipment Cleanup<br />
Provide Identification tag to new and existing equipment throughout the facility: approx. 100 tags<br />
Clean debris from existing electrical enclosures throughout the facility: approx. 30 enclosures.<br />
Correct panel grounding, terminate cable directly to existing panel s ground bar: approx. 30 panels.</p>

<p>ALTERNATE NO.1: BASE BID except delete Bldg 1, Floor 1 and Floor 3 of deficiency item 134 which directs the contractor to provide ground conductors in existing conduit. Which is noted on Sheet B01-E200.<br />
&nbsp;</p>

Point of Contact
  • Angelo Harris — angelo.harris@va.gov — 910-488-2120
View on SAM.gov

https://sam.gov/workspace/contract/opp/33cea54e56594fd4a20fb45b1905b49a/view

Register free to unlock full details

Full description, point of contact, and the direct SAM.gov link are visible with a free account.

Start Free 10-Day Trial
Details
NAICS
236220
Set-Aside
Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
Posted
2026-11-05
Deadline
Dec 8, 2026
Solicitation #
36C24627B0001
Want these matched automatically?

Add your NAICS codes and get opportunities like this emailed to you daily.

Start Free Trial